Alarm Notification System - Alerts by Phone, Email or SMS-Text

The Alarm Notification System will send alarm notifications to off-site operators by any of phone, email, pager message or SMS-text. Operators will see or hear the details of active alarms and (optionally) may acknowledge those alarms using the same format with which the alarm was sent.

This feature is an optional part of your VTScada license. Contact a representative of Trihedral Engineering Limited for further details. It is not available to VTScada Light installations.

Customers using the modem dialer feature of the Alarm Notification System must ensure that they apply Windows updates on a regular basis.
Updates to VTScada will often include modem drivers that have been patched to work with the latest Microsoft updates for your version of the Windows operating system. They may not work if you have not applied those updates to your system.

If using a voice modem, the workstation name configured in the modem tag must have fewer than 15 characters.

If running multiple applications (for example, hosted systems) then you cannot share modems, SMS devices, or Twilio accounts between applications. You must have independent modems or Twilio accounts for each application.

Only alarms with priority Critical (1) or High (2) are sent, and those only after they have gone unacknowledged for a configured length of time. The Alarm Notification System will continue to cycle through the roster in sequence until the alarm is acknowledged, or until an email, text message or pager message that is not flagged "continue sequence" is sent.

If a new alarm should occur while operators are being notified of existing alarms, or the first person in the active roster has already been informed of an existing alarm when the new alarm occurs, the Alarm Notification System will initiate a new contact to the first person on the active roster.

Having an operator sign in remotely through the Alarm Notification System does not affect the status of any operator who is logged on at the site.

The Alarms Tab of the Edit Properties Page contains several settings that control alarm notification behavior. See: Alarm Notification Options These should be reviewed before proceeding. Note that many properties can be overridden for Rosters or Alarm Databases on a case-by-case basis. See: Roster Control Using Properties

Hardware and Software Requirements:

Hardware requirements vary according to the form in which notifications are sent.

  • For spoken alarms and pager notifications, the Alarm Notification System uses either a modem or the Twilio service to make outgoing calls.
  • For email notifications, configure an email server or provide access to a commercial server such as G-Mail™ or HotMail™.
  • For SMS-text notifications, you will need a SMS appliance. Many customers find it easier to send an SMS-ready email. SMS hardware is not covered in this guide.

For the SMS text option: While VTScada will always attempt to send the text message, there is no guarantee that your the cellular provider will deliver all messages. Use the SMS option with caution.

The Roster tag will not allow you to configure a contact method that does not exist on your system. Ensure that you have at least one of the above before proceeding.

VTScada Tag Requirements:

You will need to configure some or all of the following tags in your VTScada system:

Other Configuration:

In addition to hardware and tag configuration, you may want to use the following: